Will testing the meter cause a power interruption? (WT Series)
The customer has power back for the duration of the test thanks to our internal bypasses
The only outage the customer experience is when removing the meter to inster the tester and when removing the tester to put the meter back in the installation.
The testers do not use customer load, the tester creates it's own loads with the built-in a separate three phase synthesised phantom load.
This is for all self-contained meters or any meter base that does not have meter base bypasses.
For CT rated meters, the installations bypasses shall be used to avoid opening the current transformers secondary coil.
Related Articles
Will testing the meter cause a power interruption? (NT Series)
The customer has power back for the duration of the test thanks to our internal bypasses The only outage the customer experience is when removing the meter to insert the tester and when removing the tester to put the meter back in the installation. ...
How does the ST-3/XT3 work?
ST-3/XT3 : Transformer Rated Wireless Site Tester This unit is a socket type tester, that obtains the reading directly from the secondary of the current and potential transformers. It does not require any external load to perform tests and it is ...
What is the procedure when installing the tester?
The ST-3/XT3 is compatible with CT rated installations forms 3S, 4S, 6S, 8S and 9S, it is also compatible with installation forms 5S, 35S and 45S using the included adapter. Before testing a CT rated installation in the field, always make sure that ...
Can I use it without accessories? How many accessories can I use it with?
Yes, it can work without any accessories, depending on the test you wish to perform on the site. The only test that it is not available without accessories would be the primary/secondary analysis (Ratio Test). The accessories available are 3 phases ...
What is the Secondary Burden test?
Secondary Burden test What is the Secondary Burden test? The Secondary Burden test is used to analyze the effect of a resistive burden on the behaviour of the CT. Within the ST-3/XT3 is an array of high accuracy resistors that can be, with the use of ...